AFP-400 Installation
PN 50253:A2 03/12/96
4-21
System Configuration Drawings
Use 18AWG to
12AWG twisted-pair
cable for EIA-485
connections.
AFP-400 EIA-485 Connections
Wiring Diagram
Remotely mounted serial
annunciators
ACM-32A
ACM-16AT
120-ohm end-of-line
resistors required on the
last RS-485 device.
AFP-400 EIA-485 Connections
AMG-1
CPU-400
Block Diagram for Distribution of EIA-485
Block Diagram