AFP-400 Installation
PN
50253
:
A2 03/12/96
2-63
SLC Wiring with a BGX-101L Addressable Manual Pull Station
The BGX-101L is an addressable manual pull station with a key-lock reset
feature.
1) Connect the communications loop to terminal screws (+) and ().
2) Connect the BGX-101L to the CPU-400 as listed in the table below.
Connection
Loop 1
Loop 2
Loop Out
TB5-1 (+)
TB5-3 ()
TB6-1 (+)
TB6-3 ()
Loop Return
TB5-2 (+)
TB5-4 ()
TB6-2 (+)
TB6-4 ()
3) The BGX-101L factory preset is address 00. To set the address for the
pull station, use a screwdriver to turn the rotary address switches on
the back of the BGX-101L to the appropriate settings.
BGX-101L Rotary Switches
BGX-101L Overview
Back View of the BGX-101L Pull Station
BGX-101L
Black ()
Red (+)
(+) Violet
() Yellow
BGX-101L Wiring Connections
CPU-400