AFP-400 Installation
PN
50253
:
A2 03/12/96
2-25
Terminal Assignments for Module Control of the ARM-4
Overview
The following illustration shows terminal assignments for module control of
the ARM-4 Auxiliary Relay Module
Relays K1-K4 are installed to control non-power limited circuits. Wiring
requirements follow:
Power limited and nonpower limited circuit wiring must remain separated
in the cabinet.
All power limited circuit wiring must remain at least 0.25 inches away from
any nonpower limited circuit wiring.
All power limited and nonpower limited circuit wiring must enter and exit
the cabinet though different knockouts, conduits, or both.
Contact ratings for relays K1-K4 follow.
Resistive
Load
Contacts
N.O. N.C.
125 VAC
20A 10A
30 VDC
20A 10A
For more information, refer to
Appendix F, UL Power Limited
Wiring Requirements.
ARM-4 Terminal
Assignments
ARM-4 Terminal Assignments
ARM-4 K1-K4 Contact Ratings