2-28
AFP-400 Installation
PN
50253
:
A2 03/12/96
Field Wiring the MPS-400 Power Supply
The following drawing shows the terminal blocks used to wire the MPS-400
power supply. The drawing also identifies relay switches (S4 and S5) and
LEDs for ground fault, AC power on, and Notification Appliance Circuits 1-4.
The following table lists the functions for the terminal blocks.
Voltage Select
switch
115V/230V
Mounting
Neutral
Earth
Hot
Mounting
+24 VDC battery
24 VDC battery
MPS-400 Terminal Blocks
and LEDs
Warning:
Before applying AC
power, set the 115V/230V
Voltage Select switch to the
proper voltage.
!
1 2 3 4 5 6 7
TB7(NAC1) TB9(NAC2)
S5 (Sec.)
S4 (Sup.)
JP1 Local
charger
JP5
TB8
(NAC3)
TB3
TB4
TB5
TB6
TB2 24VDC
Power Out
Ground
Fault
AC Power
On
TB10
(NAC3)
Terminal Function
TB1
Power Input 120/240VAC,50/60 Hz.
TB2
24 VDC Power out the total available power limited by power supply.
TB3TB6
Relays (dry contacts): TB3 (Alarm); TB4 (Trouble); TB5 (Supervisory);
TB6 (Security). Use SW4 or SW5 to select relay functions. (Refer to
Output Circuits.)
TB7TB10 NAC/Releasing circuits: TB7 NAC1; TB8 NAC3; TB9 NAC 2;
TB10 NAC 4. The labels shown for TB7 and TB9 apply to all four
NAC circuits.
N
O
NC C
N
O
NC C
N
O
NC C
N
O
NC C
B+ B A+ A
B+ B A+ A
+ 1.25 A max. non-resetable 1.25 A max. non-res 1.25 A max. non-resetable 1.25 A max. non-res 1.25 A max. resetable 1.25 A max. resetable
1 2 3 4 5 6
1
+
NAC/Releasing output (source)
2
NAC/Releasing output (source)
3 +
Class A (return)
4
Class A (return)
1
+
NAC/Releasing output (source)
2
NAC/Releasing output (source)
3 +
Class A (return)
4
Class A (return)
MPS-400 Power Supply Board
Refer to Power Connec-
tions and Output
Circuits for more
information on MPS-400
connections.
B+ B A+ A
B+ B A+ A
NAC2 LED
NAC3 LED
JP2 (Ground
Fault Disable)