5-14
AFP-400 Installation
PN 50253:A2 03/12/96
Zone Coding, continued
Wiring 12 Coded
Notification Appliance
Circuits (NACs)
Block Diagram
Vertical
Connection
Horizontal
Connection
MPS-400
TB-1
P9
P11
P10
P8
UZC-256
AVPS-24
#1
AVPS-24
#2
P3
J3
P3
3A Max.
3A Max.
3A Max.
Cable P/N
71093
J5
J5
J6
ICM-4
J6
ICE-4
These four Notifica-
tion Appliance
Circuits share 3 amps
and are powered from
AVPS-24 #1.
These four Notifica-
tion Appliance
Circuits share 3 amps
and are powered from
AVPS-24 #2.
Typical Wiring for 12 Zone Codes
These four coded Notification Appliance Circuits
are powered from the MPS-400. The combined
alarm load on the MPS-400 cannot exceed 6 amps.
Each NAC is rated at 2.5 amps maximum.
This section contains information for wiring modules for 12 coded Notifica-
tion Appliance Circuits (NACs). The connection table contains a list of
connections between the modules and the UZC-256. (All cables are PN
71091, except the cable between the MPS-400 and the UZC-256.) Refer to
the block diagram for typical connections. Make sure to mate all connectors
(except MPS-400, J3) as shown in the figure to the left of the block diagram.
Module
Connector Connects to UZC-256...
AVPS-24 #1
P3
P11
AVPS-24 #1
P3
P9
ICM-4
J5
P10
ICE-4
J5
P8
MPS-400
J3
TB1-8 (black wire)
TB1-7
12-Zone Code Connection Table