Settings
5. Settings
Digitax SF
Instruction Manual
5. Parameters
5.
Parameters
No. 363.0
Position
error
warning detection:
Value
Range
Default
Characteristics
0 to 2,147,483,647
100
[pulse]
Function
Use
Set the value to
determine the
position
error
warning
level
.
The position
error
warning will be detected when the position
error
exceeds this parameter
value.
Prerequisite
Position error detection: Switch (65.0) = 2 (Warning output), or 3 (Alarm and Warning output)
Related To
No. 65.0, No. 365.0
No. 365.0
Position
error
warning detection:
Delay time
Range
Default
Characteristics
0 to 65,535
(See below)
Function
Use
Set the delay time to
determine
the position
error
warning
detection time
.
Motor Capacity
Default
Units
Converted to Time
50 W to 750 W
250
160 µs
40 [ms]
1 kW to 2 kW
200
200 µs
Prerequisite
Position error detection: Switch (65.0) = 2 (Warning output), or 3 (Alarm and Warning output)
Related To
No. 65.0, No. 363.0
No. 385.0
JOG operation:
Acceleration time
Range
Default
Characteristics
0 to 60,000
1,000
[ms]
Function
Use
Set the acceleration time for JOG operation.
This item indicates the amount of time for a speed command to change from 0
rpm
to 1,000
rpm
.
With the default setting, it takes the rotational speed 3,000 ms to reach 3,000
rpm
.
Related To
JOG operation requires control power supply and the Servo ON signal input from the I/O connector.
No. 386.0
JOG operation:
Deceleration time
Range
Default
Characteristics
0 to 60,000
1,000
[ms]
Function
Use
Set the deceleration time for JOG operation.
This item indicates the amount of time for a speed command to change from 1,000
rpm
to 0
rpm
.
With the default setting, when the motor is rotating at 3,000 [
rpm
], it takes 3,000 [ms] to stop.
Remark
JOG operation requires control power supply and the Servo ON signal input from the I/O connector.
No. 387.0
JOG operation:
Target speed
Range
Default
Characteristics
0 to
Maximum Rotational Speed of Motor
300
[
rpm
]
Function
Use
Set the target speed for JOG operation.
Motor Model
Maximum rotational speed [
rpm
]
6,000
MM500,
MY500,
MM101,
MY101,
MX201,
MZ201,
MX401,
MZ401,
MX751,
MZ751
MA201, MH201, MA401, MH401
5,000
MA751, MH751
4,500
MM102, MH102, MM152, MH152, MM202
3,000
Remark
JOG operation requires control power supply and the Servo ON signal input from the I/O connector.
-
-
-
-
-
Содержание Control Techniques Digitax-SF DA21223
Страница 1: ...Instruction Manual AC SERVO MOTOR and SERVO DRIVE Series Digitax SF Part Number 0478 0606 01 Issue 1 ...
Страница 6: ...6 MEMO Digitax SF Instruction Manual ...
Страница 23: ...17 MEMO Digitax SF Instruction Manual 1 Before Use 2 Overview ...
Страница 138: ...5 5 Settings 1 Overview 2 3 3 4 4 5 6 7 17 19 20 21 22 23 24 27 28 30 34 39 52 64 68 76 82 84 88 96 98 ...
Страница 283: ...48 MEMO Digitax SF Instruction Manual 6 Operation 5 Position Control Mode ...
Страница 329: ...46 MEMO Digitax SF Instruction Manual 7 Tuning ...
Страница 330: ...8 8 Troubleshooting 2 2 4 5 5 6 8 8 9 17 18 19 20 21 22 23 ...
Страница 353: ...24 MEMO 8 Troubleshooting Digitx SF Instruction Manual ...
Страница 386: ...Digitax SF Instruction Manual 0478 0606 01 ...