4. Connection
s
Digitax SF
Instruction Man
ual
5. Descriptions of CN1 Connector Signals
RS
Connection to RS-485 circuit
Control Mode
P
S
T
RS-485 communications with the host controller
When connecting multiple
drives
, be sure to install a termination resistor of approximately
200 Ω between signal lines of the end
drive
.
Be sure to connect a pull-up resistor (RPU) and a pull-down resistor (RPD) of approximately
1.2 k Ω inside the host controller. Be sure to connect a termination resistor of approximately
220 Ω .
Make the wiring between the host controller and the
drive
less than 3m.
Between
drives
, make it less than 1m.
Signal ground of communication IC of the
drive
is connected to signal ground inside the
drive
. Connect signal ground of communications IC of the host controller to Pin No.45.
Be sure to use shielded twisted-pair cable as a noise countermeasure.
SG
5V
œőŖ
œŕ
œőŅ
ġĵĴ
ȁȪĵĹĶȫ
ġĵĵ
ȁȪİĵĹĶȫ
SG
ġĵĶ
ȁȪŔňȫ
FG
œŕ
Host Controller
Shield
Twisted-pair cable
Drive
dif.
24
5
i/o
䐟
䐠
䐡
䐢
v
olt
v
olt
Содержание Control Techniques Digitax-SF DA21223
Страница 1: ...Instruction Manual AC SERVO MOTOR and SERVO DRIVE Series Digitax SF Part Number 0478 0606 01 Issue 1 ...
Страница 6: ...6 MEMO Digitax SF Instruction Manual ...
Страница 23: ...17 MEMO Digitax SF Instruction Manual 1 Before Use 2 Overview ...
Страница 138: ...5 5 Settings 1 Overview 2 3 3 4 4 5 6 7 17 19 20 21 22 23 24 27 28 30 34 39 52 64 68 76 82 84 88 96 98 ...
Страница 283: ...48 MEMO Digitax SF Instruction Manual 6 Operation 5 Position Control Mode ...
Страница 329: ...46 MEMO Digitax SF Instruction Manual 7 Tuning ...
Страница 330: ...8 8 Troubleshooting 2 2 4 5 5 6 8 8 9 17 18 19 20 21 22 23 ...
Страница 353: ...24 MEMO 8 Troubleshooting Digitx SF Instruction Manual ...
Страница 386: ...Digitax SF Instruction Manual 0478 0606 01 ...