3. Preparation
Digitax SF Instruction Manual
2. System Wiring
*)Should you use a cable longer than the specification, please contact us in advance.
AC Suppl
y
Control power
Cables
(*)
Please use this product in the power supply environment of Over-Voltage Category Ⅱ defined by
IEC60664-1. This is the
AC Supply
for
drives
.
50 W to 750 W
Drives
:Single-phase AC200 V -10 % to AC240 V +10 %
1 kW to 2 kW
Drives
:Three-phase AC200 V -10 % to AC240 V +10 %
Using a
n
overvoltage protection relay is recommended.
When having single-phase power wired to a 1 kW
drive
, wire the primary circuit AC200 V between the L1
and L3 terminals of the
drive
.
To avoid unbalance of the three-phase AC200 V wiring in your factory, we recommend that you consider
balance of
cur
rent
in your three-phase wirings.
Confirm that your contract with the electric power company is not limited to use of three-phase.
This is power supply of DC24 V±10 % for
drive
control power, I/O power and motor brake release power.
Use a SELV (Safety Extra Low Voltage) power supply with reinforced insulation against hazardous voltages. Be
sure to connect a varistor to the motor brak
e
release power supply.
Use of UL wires and cables suitable for motor rated output are recommended.
High-voltage cables and
Ground/Earth
FG cables:
AWG18 / 600 V breakdown voltage or equivalent for 50 W to 750 W
AWG14 / 600 V breakdown voltage or equivalent for 1 kW to 2 kW
Motor power cables:
AWG18 / 300 V breakdown voltage or equivalent for 50 W to 750 W
AWG14 / 300 V breakdown voltage or equivalent for 1 kW to 2 kW
Encoder cables:
AWG22 and AWG24 compound / 30 V breakdown voltage or equivalent
Shielded cables with twisted pair wires
Length not exceeding 20 m
User I/O cable:
AWG26 / 300 V breakdown voltage or equivalent
Shielded cables with twisted pair wires
Length not exceeding 2 m
Circuit breaker
To protect the power supply line, circuit breakers shut the circuit down in the event of over-current.
Be sure to use an IEC standard and UL-certified circuit breaker between the power supply and the
EMC
noise
filter. To ensure compliance with EMC, use an earth leakage circuit breaker that we recommend.
Recommended
Product
Fuji Electric Co Ltd
Single-phase:EW32AAG-2P020B
Three-phase:EW32AAG-3P020B
20 A for single-phase (three-phase) 200 V
Leakage current of 30 mA. An equivalent product is acceptable
Select the capacity and other characteristics according to your entire system configuration.
2. Connecting Equipment and Recommended Peripherals
3
Preparation
2.
System Wiring
Содержание Control Techniques Digitax-SF DA21223
Страница 1: ...Instruction Manual AC SERVO MOTOR and SERVO DRIVE Series Digitax SF Part Number 0478 0606 01 Issue 1 ...
Страница 6: ...6 MEMO Digitax SF Instruction Manual ...
Страница 23: ...17 MEMO Digitax SF Instruction Manual 1 Before Use 2 Overview ...
Страница 138: ...5 5 Settings 1 Overview 2 3 3 4 4 5 6 7 17 19 20 21 22 23 24 27 28 30 34 39 52 64 68 76 82 84 88 96 98 ...
Страница 283: ...48 MEMO Digitax SF Instruction Manual 6 Operation 5 Position Control Mode ...
Страница 329: ...46 MEMO Digitax SF Instruction Manual 7 Tuning ...
Страница 330: ...8 8 Troubleshooting 2 2 4 5 5 6 8 8 9 17 18 19 20 21 22 23 ...
Страница 353: ...24 MEMO 8 Troubleshooting Digitx SF Instruction Manual ...
Страница 386: ...Digitax SF Instruction Manual 0478 0606 01 ...