4.2 Using Sequence Function
KP3000S
69
Table 4-1 Wattage Limiter Value per Phase
Rated output per phase
Wattage limiter value
(reference value)
Numb
er
of
power
units
per phase
1
1.5 kVA
1.575 kW
2
3 kVA
3.150 kW
--------
Notes
------------------------------------------------------------------------------------------------------------
If the wattage limiter operates, suppress the output wattage within the rated output power by
lowering the output voltage setting value.
Active power (unit: W) is restricted by the wattage limiter, however, reactive power (unit: var)
is not restricted. Therefore, the apparent power (unit: VA) may exceed the rated power
depending on the power factor of the load. Set the output voltage so that the apparent power
does not exceed the rated power, regardless of the operation of the wattage limiter.
The value of the wattage limiter cannot be changed. To limit the output power to a value that is
lower than the rating, decrease the number of power units that are energized through the power
unit energization setting, or use the peak current limiter or the RMS current limiter.
-----------------------------------------------------------------------------------------------------------------------------
4.2
Using Sequence Function
4.2.1 Basics
By using Sequence function, an output setting can be changed step-by-step according to the program
(sequence) created beforehand. This section describes the basics for using the Sequence function.
AC/DC Mode and Signal Source
Sequence function keeps the selection of the AC/DC mode and a signal source, independently from
continuous output function/Simulation function. AC/DC mode can be selected from AC/ACDC/DC.
A signal source is fixed as INT.
Keep a sequence setting
The sequence setting is kept per AC/DC mode. Every time AC/DC mode is changed, the sequence
setting that is already kept is loaded. The sequence setting is cleared when the power is turned off.
To save the setting, you need to save it in internal memory or USB memory (see
4.9
).
Содержание KP3000S
Страница 1: ...PROGRAMMABLE AC DC POWER SOURCE KP3000S INSTRUCTION MANUAL NF Corporation...
Страница 2: ......
Страница 3: ...DA00030908 004 PROGRAMMABLE AC DC POWER SOURCE KP3000S INSTRUCTION MANUAL...
Страница 4: ......
Страница 19: ...KP3000S 1 1 Outline 1 1 Overview 2 1 2 Polyphase System Configuration 2 1 3 Features 2...
Страница 22: ......
Страница 42: ......
Страница 78: ......
Страница 210: ......
Страница 211: ...KP3000S 193 5 Description of Screen and Menu 5 1 Screen Configuration 194 5 2 Menu Composition 198...
Страница 220: ......
Страница 221: ...KP3000S 203 6 Remote Control 6 1 Communication Interface 204 6 2 Remote Local State Switching 210...
Страница 233: ...KP3000S 215 8 Troubleshooting 8 1 Error Messages and Error Handling 216 8 2 When a Failure is Suspected 223...
Страница 252: ......
Страница 286: ......
Страница 288: ......
Страница 289: ......
Страница 290: ...http www nfcorp co jp NF Corporation 6 3 20 Tsunashima Higashi Kohoku ku Yokohama 223 8508 JAPAN...