background image

SPECIFICATIONS

Model EL250 

EL1000

Output Rating @ 230V  (VA) 

250 

1000

Output Current Rating (Amps)  

1.1 

4.35

Input Voltage (VAC)  

200-240 

200-240

Input Frequency (Hz) 

50-60 

50-60

Operating Temperature  

0-30 

0-30

(non-condensing) °C 
Output Voltage (VAC) 

As Input 

As Input

Load Regulation 

±3% 

±1,5%

Inrush Capacity – ½ cycle (Amps) 

35 

150

Inrush Capacity – 1 sec (Amps) 

25

Inrush Capacity – 10 secs (Amps) 

17

Forward Transfer Impedance @ 1kHz  

25 

Ω

 11 

Ω

Output Current Crest Factor for 10% (max) drop in peak voltage  

3

Efficiency at 80% load 

92% 

95%

Earth Leakage Current (typical) (µA) 

50 

75

50-ohm Attenuation
Normal-Mode 100kHz 

60dB 

60dB

Normal-Mode  30kHz-30MHz 

>40dB 

>40dB

Common-Mode 0-1MHz 

>60dB 

>60dB

Common-Mode  0-30MHz                                             

>30dB 

>30dB

0.1µs/100kHz 6kV Ring-Wave attenuation NM 

< 6V 

< 6V

0.1µs/100kHz 6kV Ring-Wave attenuation CM 

< 1V 

< 1V

Ground-Watch ® Impedance 

>500 

Ω

 >500 

Ω

10KHz-10MHz 
Output receptacle type 

IEC320 

IEC320

Number of Output Receptacles 

4

Size  w x d x h (mm) 

222x160x130 

306x230x180

Wall-mount screw spacing (mm) 

120 

190

Weight (net)  (kg) 

5.25 

19

Fuse 20x5mm HBC (ceramic) Type T 

3.15A 

10A

© Elinex Power Solutions b.v.

 www.elinex.com 

 

                                                                                 

3516 Iss 5

The Elinex Low Impedance AC Power Conditioner provides 
super-clean electrical power to sensitive electronic 
equipment. Unlike ordinary power conditioners, its 
low transfer impedance does not restrict the harmonic 
currents taken by modern switchmode power supplies, 
and its low output impedance does not magnify the 
levels 

exported

 noise always present  in your own 

equipment. It is capable of supplying the full inrush 
and surge currents taken by many types of equipment 
and therefore does not have to be de-rated for some 
applications. Unlike ordinary power-line filters, its wide 
bandwidth and non-saturable magnetic characteristics 
ensure effective elimination of noise and transient 
surges across the entire spectrum, and up to 6 kilovolts 
in amplitude.
The Elinex AC Power Conditioner provides a special 
“Local Clean Earth” independent of the signal quality of 
the building’s electrical safety earth system.  
 

www.elinex.com

Low Impedance

POWER CONDITIONER

USER INSTRUCTIONS

ELX_manual_148x210mm.indd   1-2

ELX_manual_148x210mm.indd   1-2

13-02-2009   15:39:37

13-02-2009   15:39:37

Reviews: