![Moeller DV6-340 Series Скачать руководство пользователя страница 92](http://html.mh-extra.com/html/moeller/dv6-340-series/dv6-340-series_manual_1819311092.webp)
01/02 AWB8230-1415GB
Programmable digital inputs
1 to 8
89
X
Program one of the digital inputs 1 to 8 as DB by entering the
value 07 under the corresponding PNU (C001 to C008).
X
Then, under PNU A053, enter a waiting time
t
(
a
Fig. 79)
from 0 to 5.0 s, which is to expire after activation of the DB
input before DC braking is activated.
X
Under PNU A054, enter a braking torque between 0 and
100 %.
Figure 79:
Function chart for DB (DC braking)
f
o
: Output frequency
a
Start signal through keypad
FWD/REV
DB
f
O
DB
f
O
a
DB
f
O
a
t
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616