01/02 AWB8230-1415GB
Other functions
167
The assigned external Braking resistor must not fall below the
following minimum values:
Connect the external braking resistor to terminals BR and DC+.
The maximum cable length between frequency inverter and
braking resistor must not be greater than five metres.
If you are using an external braking device, enter 0 % under
PNU b090 and remove any external braking resistors at terminals
BR and DC–.
Under PNU b095, specify when the built-in braking transistor is to
operate.
Under PNU b096, set the voltage threshold at which the built-in
braking transistor becomes active.
DV6-340-
Assigned rating at 400 V
Minimum resistance at DF
= 10 %
Minimum resistance at DF
= 100 %
kW
O
O
075
0.75
100
300
1K5
1.5
100
300
2K2
2.2
100
300
4K0
4.0
70
200
5K5
5.5
70
200
7K5
7.5
50
150
11K
11.0
50
150
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b090
Relative permis-
sible duty factor of
the built-in braking
transistor
–
j
0 to 100 %
To deactivate the relative permissible duty factor of the
built-in braking transistor, enter 0 %.
0
b095
Enable built-in
braking transistor
–
j
00
Do not enable braking transistor
00
01
Enable braking transistor in RUN mode
02
Always enable braking transistor
b096
Voltage threshold
of built-in braking
transistor
–
j
660 to 760 V
With PNU b095 = 01 or 02, the built-in braking tran-
sistor is switched in when the internal DC link voltage
reaches this value.
720