206
b090
Permissible relative percentage duty factor for built-in
braking transistor
[%]
0.00
167
b091
Type of motor stop when Off button is pressed
• 00: Braking/deceleration ramp
• 01: Free run stop
00
168
b092
Configuration of fan operation
• 00: Fan always switched on
• 01: Fan switched on only when motor running
00
168
b095
Enable built-in braking transistor
• 00: Not enabled
• 01: Enabled in RUN mode
• 02: Always enabled
00
167
b096
Voltage threshold for braking transistor
[V]
720
167
b098
Selection of PCT or NTC
• 00: No temperature monitoring
• 01: PTC
• 02: NTC
00
82
b099
Resistance threshold for thermistor input
[
O
]
3000
82
b100
User-definable
U
/
f
characteristics, frequency
coordinates 1
[Hz]
0
128
b101
User-definable
U
/
f
characteristics, voltage
coordinates 1
[V]
0.0
128
b102
User-definable
U
/
f
characteristics, frequency
coordinates 2
[Hz]
0
128
b103
User-definable
U
/
f
characteristics, voltage
coordinates 2
[V]
0.0
128
b104
User-definable
U
/
f
characteristics, frequency
coordinates 3
[Hz]
0
128
b105
User-definable
U
/
f
characteristics, voltage
coordinates 3
[V]
0.0
128
b106
User-definable
U
/
f
characteristics, frequency
coordinates 4
[Hz]
0
128
b107
User-definable
U
/
f
characteristics, voltage
coordinates 4
[V]
0.0
128
b108
User-definable
U
/
f
characteristics, frequency
coordinates 5
[Hz]
0
128
b109
User-definable
U
/
f
characteristics, voltage
coordinates 5
[V]
0.0
128
b110
User-definable
U
/
f
characteristics, frequency
coordinates 6
[Hz]
0
128
b111
User-definable V/f characteristics, voltage
coordinates 6
[V]
0.0
128
b112
User-definable
U
/
f
characteristics, frequency
coordinates 7
[Hz]
0
128
b113
User-definable
U
/
f
characteristics, voltage
coordinates 7
[V]
0.0
129
b120
Brake control
• 00: Not active
• 01: Active
00
170
b121
Brake released confirmation waiting time
[s]
0.00
170
b122
Waiting time before acceleration
[s]
0.00
170
PNU
Function
Units
Default
Page
Setpoint
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616