![Moeller DV6-340 Series Скачать руководство пользователя страница 206](http://html.mh-extra.com/html/moeller/dv6-340-series/dv6-340-series_manual_1819311206.webp)
01/02 AWB8230-1415GB
Standard form for user defined
parameter settings
203
A103
Analog input OI starting current
[%]
20
64
A104
Analog input OI end current
[%]
100
64
A105
Analog input OI condition for starting frequency
00: Start at PNU A101
02: Start at 0 Hz
01
64
A111
Analog input O2 starting frequency
[Hz]
0.00
65
A112
Analog input O2 end frequency
[Hz]
0.00
65
A113
Analog input O2 starting voltage
[%]
–100
65
A114
Analog input O2 end voltage
[%]
100
65
A131
Curvature of acceleration characteristic, values from 01
to 10
02
150
A132
Curvature of deceleration characteristic, values from 01
to 10
02
150
PNU
Function
Units
Default
Page
Setpoint
PNU
Function
Units
Default
Page
Setpoint
b001
Restart mode
• 00: Fault message
• 01: 0 Hz Start
• 02: Synchronization to current motor speed and
acceleration
• 03: Synchronization and deceleration
00
153
b002
Permissible power failure duration
[s]
1.0
153
b003
Waiting time before restart
[s]
1.0
153
b004
Fault message issued immediately
• 00:
No
fault on intermittent mains failure
• 01: Fault on intermittent mains failure
• 02:
No
fault on intermittent mains failure at stand-
still and deceleration
00
153
b005
Number of restart attempts
• 00: 16 restart attempts
• 01: Unlimited number of restart attempts
00
153
b006
Mains phase failure detection
• 00: Not active
• 01: Active
00
153
b007
Synchronization frequency on return of mains power
[Hz]
0.00
153
b012
Tripping current for electronic motor protection device
[A]
I
e
(inverter)
156
b212
Tripping current for electronic motor protection device
(second parameter set)
[A]
I
e
(inverter)
156
b312
Tripping current for electronic motor protection device
(third parameter set)
[A]
I
e
(inverter)
156
b013
Characteristic for electronic motor protection device
• 00: Enhanced protection
• 01: Normal protection
• 03: User-definable protection
01
156
b213
Characteristic for electronic motor protection device
(second parameter set)
• 00: Enhanced protection
• 01: Normal protection
• 03: User-definable protection
01
156
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616