Setting Parameters
01/02 AWB8230-1415GB
168
Type of motor stop
Specify here, how the motor is to decelerate when the OFF button
is pressed:
Fan control
With PNU b092, you can specify when the fan will operate.
If you enter the value 01 here, the fan runs for one minute after
the frequency inverter power supply is switched on, allowing you
to make sure that the fan is working correctly. The fan also conti-
nues to run for five minutes after the connected motor has stopped
to dissipate residual heat.
Debug mode
Under PNU C091, set debug mode.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b091
Type of motor
stop
–
–
00
Deceleration using the deceleration ramp
00
01
Free run stop (coasting)
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b092
Fan control
–
–
00
Fan is always switched on
00
01
Fan is switched on only while the connected motor is
running.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
C091
Debug mode
–
j
00
Debug mode is displayed.
00
01
Debug mode is
not
displayed.