![Moeller DV6-340 Series Скачать руководство пользователя страница 166](http://html.mh-extra.com/html/moeller/dv6-340-series/dv6-340-series_manual_1819311166.webp)
01/02 AWB8230-1415GB
Other functions
163
Display mode
With this function, you can specify the parameters which the DV6
displays. Only these displayed parameters can then be changed:
• All parameters: PNU b037 = 00 (default)
• Parameters which are relevant to the programmed parameters:
PNU b037 = 01
• Only the parameters saved under PNU U001 to U012:
PNU b0037 = 02 (
a
Section “User-defined parameters –
parameter group U“, Page 176)
All parameters: PNU b037 = 00 (default)
By default, the DV6 displays all parameters and all parameters can
be changed.
Relevant parameters: PNU b037 = 01
With this setting, the DV6 displays only those parameters which
are connected with ones that are already programmed. If, for
example you set a constant
V
/
f
characteristic under PNU A044
(default value: 00), the parameters for an adjustable
V
/
f
charac-
teristic are not shown (PNU b100 to b113). The table below
shows, which parameters are hidden when this option is set.
PNU
Value
PNUs which are hidden when PNU b037 is
set to 01
Function
A001
01
A005, A006, A011 to A016, A101 to A105, A111
to A114, C081 to C083, C121 to C123
Analog inputs O, OI, O2
A002
01, 03, 04, 05
b087
OFF key disabled
A019
00
A028 to A035
Fixed frequencies
C001 to C008
02, 03, 04, 05
A044, A244
02
b100 to b113
Voltage and frequency characteristic
A051
01
A052 to A059
DC braking
A071
01
A072 to A076, C044
PID control
A094
01
A095 to A096
Second time ramp
A294
01
A295 to A296
b013, b213, b313
02
b015 to b020
Electronic motor protection
b021
01, 02
b022, b023
Overcurrent limit
b024
01, 02
b025, b026
Overcurrent limit 2
b095
01, 02
b090, b096
BRD function
C001 to C008
06
A038, A039
Jog mode
08
F202, F203, A203, A204, A220, A241 to A244,
A261, A262, A292 to A296, b212, b213, H202 to
H206, H220 to H224, H230 to H234, H250 to
H252, H260
Second parameter set
11
b088
Motor shutdown and free run stop
17
F302, F303, A303, A304, A320, A342 to A344,
A392, A393, b312, b313, H306
third parameter set
18
C102
Reset
27, 28, 29
C101
Acceleration/deceleration motor potentiometer
A044
00, 01
A041 to A043
Voltage boost function
04
H060
0 Hz limitation
A244
00, 01
A241 to A243
Voltage boost function
04
H260
0 Hz limitation
A044
03, 04, 05
b040 to b046, H001, H002, H005, H020 to H024,
H030 to H034, H050 to H052, H060, H070 to
H072
A244
03, 04
b040 to b046, H202, H205, H220 to H224, H230
to H234, H250 to H252, H260, H070 to H072
A097
01, 02, 03
A131
Curvature of acceleration ramp
A098
01, 02, 03
A132
Curvature of acceleration ramp
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616