01/02 AWB8230-1415GB
Programmable digital inputs
1 to 8
81
Change over vector parameters (CAS)
Activating the digital input configured as CAS causes a change-
over between the PI control parameters. PI control regulates the
speed and is available only in vector control mode (PNU A044)
(
a
Section “Voltage/frequency characteristic and voltage
boost“, Page 126):
• SLV control
• 0 Hz SLV control
• Vector control with optional DE6-IOM-ENC module
When the CAS input is inactive or no digital input is configured as
CAS, the following paramaters apply:
• PNU H050 (H250),
• PNU H051 (H251),
• PNU H052 (H252).
When the CAS input is active, the following parameters apply:
• PNU H070,
• PNU H071,
• PNU H072.
X
To activate vector control, enter one of the following values
under PNU A044 (
a
Section “Voltage/frequency charac-
teristic and voltage boost“, Page 126).
– 03: SLV control
– 04: 0 Hz SLV control
– 05: Vector control with optional DE6-IOM-ENC module.
X
Program one of the digital inputs 1 to 8 as CAS by setting the
corresponding PNU (C001 to C008) to 26.
Figure 72:
Digital input 1 configured as REV (start/stop anticlockwise
operation) and 2 as CAS (change over vector parameters).
CAS
REV
P24
FW
1
2
CAS
PNU
Active
H050 (H250)
j
H051 (H251)
j
H052 (H251)
j
H070
–
H071
–
H072
–
H050 (H250)
–
H051 (H251)
–
H052 (H251)
–
H070
j
H071
j
H072
j
CAS
P24
2
CAS
P24
2
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
A044
A244
A344
Voltage/frequency
characteristic
–
–
00
V
/
f
characteristic, linear
00
01
V
/
f
characteristic, quadratic, for example fans
02
User-definable
03
Sensorless vector control (SLV)
1)
04
0 Hz SLV control
1)
05
Vector control
1)
with optional DE6-IOM-ENC module
H005
Motor constants
j
j
0.001 to 65.53
Gain Kp
1.590
H050
PI proportional gain
j
j
0.00 to 1000 %
P component of he PI control in vector control mode
100.0
H051
PI Integration gain
j
j
0.00 to 1000 %
I component of he PI control in vector control mode
100.0
H052
P proportional gain
j
j
0.01 to 10.00
P component of he P control in vector control mode
1.00
H070
PI proportional gain
j
j
0.00 to 1000 %
P component of he PI control in vector control mode
100.0
H071
PI Integration gain
j
j
0.00 to 1000 %
I component of he PI control in vector control mode
100.0
H072
P proportional gain
j
j
0.01 to 10.00
P component of the P control in vector control mode
1.00
1) If SLV control is active, you should set the pulse frequency to at least 2.1 kHz with PNU b083 (
a
Section “Pulse frequency“, Page 164).