![Moeller DV6-340 Series Скачать руководство пользователя страница 162](http://html.mh-extra.com/html/moeller/dv6-340-series/dv6-340-series_manual_1819311162.webp)
01/02 AWB8230-1415GB
Parameter protection
159
Parameter protection
Under PNU b031, you can specify whether you want to use the
normal or extended parameter setting features in RUN mode. If
you set the value 10 under PNU b031, further parameters are avai-
lable which can be modified in the RUN mode. These additional
parameters are marked “
j
” in the Extended column.
.
The five following methods of parameter protection are available:
Adjustable in RUN mode
Normal
Extended
–
j
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b031
Software
parameter
protection
–
j
00
Parameter protection through SFT input;
all functions inhibited
01
01
Parameter protection through SFT input;
input through PNU F01 possible
02
Parameter protection without SFT input;
all functions inhibited
03
Parameter protection without SFT input;
input through PNU F01 possible
10
Extended parameters adjustable in RUN mode
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616