Engineering
01/02 AWB8230-1415GB
14
Relay
Changeover contact
• Contacts K11-K14
– 250 V AC, 2 A (resistive load)
– 250 V AC, 0.2 A (inductive load, p.f. = 0.4)
– 100 V AC, minimum 10 mA
– 30 V DC, 8 A (resistive load)
– 30 V DC, 0.6 A (inductive load, p.f. = 0.4)
– 5 V DC, minimum 100 mA
• Contacts K11-K12
– 250 V AC, 1 A (resistive load)
– 250 V AC, 0.2 A (inductive load, p.f. = 0.4)
– 100 V AC, minimum 10 mA
– 30 V DC, 1 A (resistive load)
– 30 V DC, 0.2 A (inductive load, p.f. = 0.4)
– 5 V DC, minimum 100 mA
Internal voltages
Control
24 V DC, maximum 30 mA
Setpoint definition
10 V DC, maximum 10 mA
Analog and digital actuation
Analog inputs
• 1 input, 0 to 10 V, input impedance 10 k
O
• 1 input, 4 to 20 mA, load impedance 250
O
• 1 input, +10 to –10 V, input impedance 10 k
O
Digital inputs/outputs
8 inputs, user-configurable
5 outputs, open collector (up to 27 V DC, 50 mA), user-configurable
Analog outputs
• 1 output for motor frequency or current, 10 V, up to 1.2 mA
• 1 output, 0 to 10 V, up to 2 mA, user-configurable
• 1 output, 4 to 20 mA, user-configurable
Keypad (built-in)
Operation
6 function keys for controlling and parameterizing the DV6
Display
Four-digit, 7-segment display and ten LEDs (for status signals)
Potentiometer
Setpoint definition (0 to 270°)
1) If the frequency inverter is to be installed in a control panel, enclosure or similar installation, the temperature within the enclosure or control panel is
considered to be ambient temperature T
a
. The use of fans should be considered to ensure that the ambient temperature remains within permissible
limits.