01/02 AWB8230-1415GB
SLV and autotuning
173
The table below lists the parameters of the autotuning function.
Parameters which are only defined automatically are marked
“(autotuning)” in the Name column.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
H001
Autotuning
mode
–
–
00
Autotuning not active
00
01
Carry out autotuning (only at motor standstill)
02
Carry out autotuning with motor operation
H002
H202
Motor data to
be used
–
–
00
Use default motor data
00
01
Use autotuning data (single autotuning procedure)
02
Use autotuning data (multiple autotuning procedures)
H003
H203
Motor rating
–
–
0.2 to 160 kW
Enter the motor rating.
• 0.2 to 75 kW: DV6-340-075 to DV6-340-55K
• 0.2 to 160 kW: From DV6-340-75K
Depen-
ding on
DV6
H004
H204
Number of
motor poles
–
–
2/4/6/8
Enter the number of motor poles
4
H005
H205
Motor
constant
K
p
j
j
0.01 to 99
Motor gain factor
1.59
H006
H206
H306
Motor stabili-
zation constant
j
j
0 to 255
0 function is not active
100
H020
H220
Motor
constant
R
1
–
–
0 to 65.53
O
Stator impedance
Depen-
ding on
DV6
H021
H221
Motor
constant
R
2
1)
–
–
0 to 65.53
O
Rotor resistance
H022
H222
Motor
constant
L
–
–
0 to 655.3 mH
Motor inductivity
H023
H223
Motor
constant
I
o
–
–
0 to 655.3
A
r.m.s.
Motor current
H024
H224
Motor
constant
J
2)
–
–
1 to 1000
Moment of inertia of the motor relative to the load
H030
H230
Motor
constant
R
1
(autotuning)
–
–
–
Here, the parameters determined with autotuning are
saved. They cannot be set manually. The manually adjus-
table motor constants can be configured with PNU H20 to
H24 or H220 to H224.
Depen-
ding on
DV6
H031
H231
Motor
constant
R
2
(autotuning)
–
–
H032
H232
Motor constant
L
(autotuning)
–
–
H033
H233
Motor constant
I
o
(autotuning)
–
–
H034
H234
Motor constant
J
(autotuning)
–
–
1) In case of an over-compensation, reduce
R
2
2) The greater
J
, the slower the motor responds; the smaller
J
, the faster it
responds (
J
= moment of inertia of the motor relative to the load)