Programming the control
signal terminals
01/02 AWB8230-1415GB
118
After a fault has occurred, the associated fault message is retained
even after the voltage supply is switched off. This fault message
can therefore be recalled from fault history register when voltage
has been switched back on. However, the inverter is reset when
the device is switched off, i.e. the fault message will not be output
at the signalling relay’s terminals after the inverter is switched
back on.
Note that, when the signalling relay output is configured as a
break contact (default setting), there is a delay from the time the
supply voltage is switched on until the AL output is closed, and
that a fault message for the AL output therefore appears for a
short time after the supply is switched on.
PNU
Name
Adjustable in RUN mode
Value
Function
Page
WE
Normal
Extended
C026
Signal at
signalling relay
output
–
j
00
RUN: Operation
104
05
01
FA1: Frequency reached
102
02
FA2: Frequency exceeded
102
03
OL: Overload alarm
105
04
OD: PID system deviation exceeded
106
05
AL: Fault
107
06
FA3: Frequency (within range) reached
102
07
OTQ: Torque reached (exceeded)
110
08
IP: Mains failure, immediate stop
113
09
UV: Undervoltage
113
10
TRQ: Torque limitation
111
11
RNT: Running time exceeded
114
12
ONT: Mains On time exceeded
114
13
THM: Motor thermal overload
115
19
BRK: Enable signal for external brake
108
20
BER: Brake fault
108
21
ZS: Zero speed
–
1)
22
DSE: Speed deviation exceeded
–
1)
23
POK: Positioning
–
1)
24
FA4: Frequency exceeded
102
25
FA5: Frequency reached
102
26
OL2: Overload alarm 2
105
C036
Signalling relay
output
–
j
00
K11-K14 close with a fault message
–
01
01
K11-K14 close when the supply voltage is applied
–
1)
a
Manual AWB82401-1431... for DE6-IOM-ENC encoder module
h
If however, the fault signal is to be retained even after the
inverter is switched back on, a latching (self maintaining)
relay should be used.