01/02 AWB8230-1415GB
Technical Data
189
Torque during start
• 200 % at 0.5 Hz with SLV control
• 150 % in the range 0 to 2.5 Hz with 0 Hz range SLV
control and motor one rating class smaller than DV6
• 100 % with vector control
• 180 % at 0.5 Hz with SLV control
• 130 % in the range 0 to 2.5 Hz with 0 Hz
range SLV control and motor one rating
class smaller than DV6
• 100 % with vector control
Braking torque
with feedback in to the capacitors:
reduced braking torque at frequencies
exceeding 50 Hz.
Approx. 10 %
with external braking resistor
–
with external braking unit
35 to
200 %
110 to
170 %
90 to
150 %
70 to
120 %
60 to
100 %
45 to
70 %
40 to
60 %
30 to
50 %
25 to
40 %
with DC injection braking
Braking occurs at frequencies below the minimum frequency (minimum frequency, braking time and braking
torque are user-definable)
Inputs
Frequency setting
Keypad
Setting through keys or potentiometer
External
signals
• 0 to 10 V
H
, input impedance 10 k
O
;
• –10 V to +10 V
H
, input impedance 10 k
O
;
• 4 to 20 mA, load impedance 250
O
• Potentiometer
f
1 k
O
, recommended 4.7 k
O
Clockwise/anticlock-
wise operation (start/
stop)
Keypad
ON key (for Start) and OFF key (for Stop); default setting = clockwise operation
External
signals
• Digital input FW for clockwise operation (FWD)
• Digital input programmable as REV for anticlockwise operation
DV6-340-...
22K
30K
37K
45K
55K
75K
90K
110K
132K