01/02 AWB8230-1415GB
Setting the frequency and start
signal parameters
123
Setting the frequency and start signal parameters
This section describes the methods for adjusting and setting the
start signal and basic frequency parameters.
Definition of frequency setpoint value
With PNU A001, specify the method of defining the setpoint
frequency:
• using the potentiometer on the keypad
• through analog input O (0 to 10 V), O2 (–10 to +10 V) or OI
(4 to 20 mA)
• through PNU F001 or PNU A020
• through the RS 485 serial interface
• through slot 1 or 2 for optional modules
Start signal
With PNU A002, you specify how the start signal is to be issued:
• through digital inputs, for example the FW input or a digital
input configured as REV,
• with the ON key on the keypad,
• through the RS 485 serial interface,
• through slot 1 or 2 for optional modules.
.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
A001
Defined
frequency
setpoint
–
–
00
Definition with the potentiometer on the keypad
01
01
Definition through analog input O (0 to 10 V), O2 (
g
10 V) or
OI (4 to 20 mA)
02
Definition through PNU F001 and/or PNU A020
03
RS 485 serial interface
04
Setpoint definition through the optional module in slot 1
05
Setpoint definition through the optional module in slot 2
A020
Frequency
setpoint value
j
j
0.01 to 400 Hz
You can enter a frequency setpoint value. To do this, enter
the value 02 under PNU A001.
0.0
F001
Indication/
input of
frequency
value
j
j
Indication of the current frequency setpoint value or the
current fixed frequency.
Modified values are saved with the ENTER key according to
the selection of the digital inputs configured as FF1 to FF4
(
a
Section “Fixed frequency selection (FF1 to FF4)“,
Page 69).
Resolution
g
0.01 Hz