01/02 AWB8230-1415GB
Programmable digital outputs
11 to 15
101
Programmable digital outputs 11 to 15
Programmable digital outputs 11 to 15 are open collector tran-
sistor outputs (
a
Fig. 98), to which you can connect, for
example, relays. These outputs can be used for various functions,
for example to signal when a determined frequency setpoint is
reached or when a fault occurs.
The terminal functions for programmable digital outputs 11 to 15
are configured under PNU C021 to C025 respectively, i.e.
PNU C021 defines the function of digital output 11, PNU C022 the
function of digital output 12, etc.
Table 17:
Digital outputs 11 to 15
For a detailed description of the output functions, see the pages
listed in Table 18.
Table 18:
Functions of the digital outputs
Programmable digital outputs 11 to 15 are configured by default
as make contacts.
Optionally, you can configure the digital outputs as break (NC)
contacts. To do this, enter 01 under PNU C031 to C35 (correspon-
ding to digital outputs 11 to 15).
Table 19:
Configuration of digital outputs as make contacts
Figure 98:
Digital output
Transistor output: up to 27 V
H
, 250 mA
PNU
Ter-
minal
Adjustable in RUN
mode
Value
WE
Normal
Extended
C021
11
–
j
a
Table 18
01
C022
12
00
C023
13
03
C024
14
07
C025
15
08
Value
Function
Description
a
Page
00
RUN
Operation
104
01
FA1
Frequency setpoint reached
102
02
FA2
Frequency exceeded
102
03
OL
Overload signal
105
04
OD
PID control deviation
exceeded
106
05
AL
Fault
107
06
FA3
Frequency (within range)
reached
102
07
OTQ
Torque reached (exceeded)
110
08
IP
Mains failure, immediate stop
113
F
27 V
H
, 250 mA
11, 12, 13, 14, 15
CM2
24 V
– +
09
UV
Undervoltage signal
113
10
TRQ
Torque limitation
111
11
RNT
Running time exceeded
114
12
ONT
Mains On time exceeded
114
13
THM
Motor thermal overload
115
19
BRK
Release brake
108
20
BER
Brake fault
108
21
ZS
Zero speed
109
22
DSE
Speed deviation exceeded
–
1)
23
POK
Positioning
–
1)
24
FA4
Frequency exceeded
102
25
FA5
Frequency setpoint reached
102
26
OL2
Overload signal 2
105
1)
a
Manual AWB8230-1431.. for encoder module DE6-IOM-ENC
PNU
Ter-
minal
Value
Adjustable in
RUN mode
Function
WE
Nor-
mal
Exten-
ded
C031
11
00 or
01
–
j
00: Make
contact
01: Break
contact
00
C032
12
C033
13
C034
14
C035
15
Value
Function
Description
a
Page