01/02 AWB8230-1415GB
Analog inputs,
terminals O, O2 and OI
61
Analog inputs, terminals O, O2 and OI
You can specify the setpoint frequency through three analog
inputs:
• Terminal O: 0 to 10 V
• Terminal O2: –10 V to +10 V
• Terminal OI: 4 to 20 mA
The reference potential for the analog inputs is terminal L.
Frequency setpoint definition
By default, the frequency setpoint is defined through voltage input
O (0 to +10 V). Alternatively, you can enter the setpoint value
through one of the other analog inputs or a combination of two
analog inputs. To do this, you must configure a digital input with
the AT function (
a
Section “Analog input changeover (AT)“,
Page 73). The two inputs are specified under PNU A005 and
A006.
The table below shows how you can link analog inputs O, O2 and
OI with PNU A005 and A006.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
A005
AT selection
–
–
00
Changing over from O to OI
00
01
Changing over from O to O2
A006
O2 selection
–
–
00
O2 signal only
00
01
Sum of signals at O2 and O or OI
without
direction reversal
02
Sum of signals at O2 and O or OI
with
direction reversal
Main frequency
setpoint value
input
O2 signal sum
Reversal of
direction with
O2
AT input
configured
A006
A005
Input AT
O
Yes
Yes
Yes
02
00
OFF
01
No
Yes
01
00
OFF
01
No
No
Yes
00
00
OFF
00
01
Add O + OI
Yes
Yes
No
00
–
–
02
No
01
O2
No
Yes
Yes
02
01
ON
00
No
01
OI
Yes
Yes
Yes
02
00
ON
Yes
No
01
No
No
00