Programming the control
signal terminals
01/02 AWB8230-1415GB
102
Frequency arrival signal FA1/FA2/FA3/FA4/FA5
The digital output configured as FA1 is activated as soon as the
setpoint frequency is reached (
a
Fig. 99).
The digital output configured as FA2 is active while the frequen-
cies defined under PNU C042 and C043 are exceeded
(
a
Fig. 101).
The digital output configured as FA3 is activated when the
frequency defined under PNU C042 is reached during acceleration.
As soon as this frequency is left, FA3 is deactivated again. During
deceleration, FA3 responds in the same way at the frequency set
under PNU C043 (
a
Fig. 102).
The digital output configured as FA4 is active while the frequen-
cies defined under PNU C045 and C046 are exceeded
(
a
Fig. 101).
The digital output configured as FA5 is activated when the
frequency defined under PNU C045 is reached during acceleration.
As soon as this frequency is left, FA3 is deactivated again. During
deceleration, FA3 responds in the same way at the frequency set
under PNU C046 (
a
Fig. 102).
To achieve a certain hysteresis, signals FA1 to FA5 are each acti-
vated with
f
1
before the switching threshold is reached and deac-
tivated again with
f
2
on leaving the switching threshold.
f
1
and
f
2
are:
•
f
1
= 1 % of the end frequency (PNU A004, A204, A304)
•
f
2
= 2 % of the end frequency (PNU A004, A204, A304)
X
To configure a programmable output as FA2, set the frequency
under PNU C042, at which the FA2 signal is to be generated in
the acceleration phase.
X
With PNU C043, set the respective frequency which is to remain
active until the FA2 signal is deactivated during deceleration.
Figure 99:
Function chart for FA1 (frequency reached)
f
o
:
Output frequency
f
1
:
1 % of the end frequency (PNU A004, A204, A304)
f
2
:
2 % of the end frequency (PNU A004, A204, A304)
F001: Setpoint value
FA1
PNU F001
f
O
f
1
f
2
t
Figure 100: Digital output 11 configured as FA1/FA2 (frequency
reached/exceeded)
Figure 101: Function chart for FA2 (frequency exceeded)/FA4
f
o
: Output frequency
f
1
: 1 % of the end frequency (PNU A004, A204, A304)
f
2
: 2 % of the end frequency (PNU A004, A204, A304)
Figure 102: Function chart for FA3 (frequency reached)/FA5
f
o
: Output frequency
f
1
: 1 % of the end frequency (PNU A004, A204, A304)
f
2
: 2 % of the end frequency (PNU A004, A204, A304)
FA1/FA2
24 V
50 mA
11
CM2
12
13
14
15
–
+
FA2/FA4
PNU C042/C045
PNU C043/C046
f
O
f
1
f
2
FA3/FA5
f
O
PNU C042/C045
PNU C043/C046
f
1
f
1
f
2
f
2