01/02 AWB8230-1415GB
Voltage/frequency charac-
teristic and voltage boost
127
Quadratic
V
/
f
characteristic
For a reduced torque, enter the value 01 under PNU A044. The
DV6 frequency inverter then increases the output voltage
V
2
on
a linear ramp up to ten percent of the base frequency in
PNU A003. Then, the DV6 increases
V
2
on a quadratic ramp
(reduced) to the transition frequency in PNU A003.
Adjustable
V
/
f
characteristic
For a freely programmable torque, enter the value 02 under
PNU A044. Under PNU b100 to b113, you can assign seven diffe-
rent frequency-voltage pairs to the DV6. However, the frequencies
f
1
to
f
7
must have increasing values for this:
f
1
F
f
2
F
f
3
F
...
F
f
7
. The voltages
V
1o
to
V
7o
are freely adjustable.
f
7
can be up to the maximum frequency of the DV6.
V
7o
can be
up to the input voltage
V
1
or the voltages set under PNU A082.
If you use the adjustable
V
/
f
characteristic, the following para-
meters are no longer valid:
• PNU A003: Base frequency
• PNU A004: End frequency
• PNU A041: Voltage boost characteristic
Figure 124: Linear
V
/
f
characteristic
V
2
:Output voltage
f
O
: Output frequency
Figure 125: Quadratic
V
/
f
characteristic
V
2
:Output voltage
f
O
: Output frequency
PNU A003
PNU A004
100
[%]
U
2
f
o
PNU A003
0.1
x
PNU A003
PNU A004
100
[%]
U
2
f
o
Figure 126: Adjustable
V
/
f
characteristic
V
2
:Output voltage
f
O
: Output frequency
Figure 127: Limits of the freely adjustable
V
/
f
characteristic
V
2
:Output voltage
f
O
: Output frequency
PNU b113
U
7o
PNU b111
U
6o
PNU b109
U
5o
PNU b107
U
4o
PNU b101
U
1o
PNU b103
U
2o
PNU b105
U
3o
f
1
f
2
f
3
f
4
f
5
f
6
f
7
PNU b100 b102
b104
b106
b108 b110 b112
U
2
f
o
f
1
f
6
f
7
.
.
.
.
.
.
.
.
.
.
400
U
1
, PNU A082
U
7o
U
6o
U
1o
U
2
f
o
[Hz]