01/02 AWB8230-1415GB
Programmable digital inputs
1 to 8
85
Behaviour on restart
With PNU C101, you can specify whether the frequency defined
with UP/DWN, or the original frequency entered under PNU A020
is used when the DV6 frequency inverter is restarted.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
C101
Use memory
–
j
00
Use original frequency set under PNU A020
00
01
Use saved UP/DWN setting