Appendix
01/02 AWB8230-1415GB
204
b313
Characteristic for electronic motor protection device
(third parameter set)
• 00: Enhanced protection
• 01: Normal protection
• 03: User-definable protection
01
156
b015
Frequency 1 for user-definable motor protection
characteristic
[Hz]
0
156
b016
Tripping current 1 for user-definable motor protection
characteristic
[A]
0.0
156
b017
Frequency 2 for user-definable motor protection
characteristic
[Hz]
0
156
b018
Tripping current 2 for user-definable motor protection
characteristic
[A]
0.0
156
b019
Frequency 3 for user-definable motor protection
characteristic
[Hz]
0
156
b020
Tripping current 3 for user-definable motor protection
characteristic
[A]
0.0
156
b021
Motor current limitation 1
• 00: Inactive
• 01: Active in every operating status
• 02: Inactive during acceleration, otherwise active
• 03: Active in every operating state; in regenerative
operation, the current is increased
• 04: Inactive during acceleration; in regenerative
operation, the current is increased
01
157
b022
Tripping current 1 for motor current limitation
[A]
I
e
x
1.5
157
b023
Time constant 1 of motor current limitation
[s]
1.00
157
b024
Motor current limitation 2
• 00: Inactive
• 01: Active in every operating status
• 02: Inactive during acceleration, otherwise active
• 03: Active in every operating state; in regenerative
operation, the current is increased
• 04: Inactive during acceleration; in regenerative
operation, the current is increased
1
158
b025
Tripping current 1 for motor current limitation
[A]
I
e
x
1.5
158
b026
Time constant 1 of motor current limitation
[s]
1.0
158
b031
Software dependent parameter protection
• 00: Via SFT input; all functions inhibited
• 01: Via SFT input; function F01 possible
• 02: Without SFT input; all functions inhibited
• 03: Without SFT input; function F01 possible
• 10: Extended parameters adjustable in RUN mode
01
159
b034
Running time or Mains On time signal
[h]
0
114
b035
Inhibit direction
00: Motor can run in both directions
01: Motor can only run clockwise
02: Motor can only run anticlockwise
00
162
b036
Voltage ramp to starting frequency
• 00: Start without voltage reduction
• 01: Minimum voltage reduction, approx. 6 ms
• ...
• 06: Maximum voltage reduction, approx. 36 ms
06
162
PNU
Function
Units
Default
Page
Setpoint