01/02 AWB8230-1415GB
Automatic restart after a fault
153
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b001
Restart mode
–
j
00
The above fault messages are displayed when the associated
fault occurs (restart is not activated).
00
01
A restart takes place at the starting frequency after the time
set under PNU b003 has elapsed.
02
After the time set under PNU b003 has elapsed, the
frequency inverter synchronizes to the current motor rota-
tion speed and the motor accelerates for the set acceleration
time.
03
After the time set under PNU b003 has elapsed, the inverter
synchronizes to the current motor rotation speed and the
motor brakes for the set deceleration time. A fault message
is then displayed.
b002
Permissible
power failure
duration
–
j
0.3 to 1.0 s
Here, set a time duration for which the undervoltage condi-
tion is met without the corresponding fault message in E09
being issued.
1.0
b003
Waiting time
before restart
–
j
0.3 to 100 s
Here, set a time which is to expire before an automatic
restart is initiated after a fault signal. This time can be used
in conjunction with the FRS function. During the waiting
time, the following message appears on the LED display:
1.0
b004
Fault message
issued immedi-
ately
–
j
00
In the event of an intermittent power supply failure or under-
voltage, the frequency inverter does
not
go into fault status.
00
01
In the event of an intermittent power supply failure or under-
voltage, the frequency inverter goes into fault status.
02
In the event of an intermittent power supply failure or under-
voltage
at standstill or during deceleration
, the
frequency inverter does
not
go into fault status.
b005
Number of
restart
attempts
–
j
00
16 restart attempts at intermittent supply failure or under-
voltage.
00
01
The number of restart attempts is not limited.
b006
Mains phase
failure
detection
1)
–
j
00
Inactive
00
01
Active
b007
Synchroniza-
tion frequency
–
j
0 to 400 Hz
When the frequency corresponding to the motor speed is
higher than the frequency programmed here, the frequency
inverter synchronizes itself with the motor speed and accele-
rates to the setpoint value.
When the frequency corresponding to the motor speed is
lower than the frequency programmed here, the frequency
inverter starts at 0 Hz.
0.00
1) Phase failure detection can not be used if you are using the DV6 frequency
inverter with an RFI filter.