01/02 AWB8230-1415GB
EMC compliance
23
With leakage currents
f
3.5 mA, VDE 0160 and EN 60335, one of
the following conditions must be fulfilled:
• the protective conductor has a cross-section
f
10 mm
2
,
• the protective conductor is monitored to ensure continuity, or
• an additional protective conductor is installed.
For DV6 frequency inverters, use the assigned DV6-LZ... filters.
EMC measures in the control panel
To ensure an EMC-compliant setup, connect all metallic compon-
ents of the devices and of the control cabinet with each other
using a large cross-section conductor with good HF conducting
properties. Do not make connections to painted surfaces (Eloxal,
yellow-passivized). If there is no alternative, use contact and
scraper washers to ensure contact with the base metal. Connect
mounting plates to each other, and the cabinet doors with the
cabinet, using contacts with large surface areas and short HF
wires.
An overview or all EMC measures can be seen in the following
figure.
Figure 13:
EMC-compliant setup
PES
PES
PES
W2 U2 V2
U1 V1 W1
PE
PE