Operating the DV6
01/02 AWB8230-1415GB
50
Connection examples
Operation using an external potentiometer
Configuration of the parameters
Method of operation
You can start the frequency inverter in a clockwise direction with
terminal FW and in an anticlockwise direction with terminal 8. If
both terminals are closed simultaneously, a stop signal is issued.
With the externally connected potentiometer, the required
frequency setpoint (voltage setpoint) can be defined.
You can use the measuring instrument to display the frequency
(PNU C023 = 00) or the motor current (PNU C023 = 01). With
PNU b081, you can match analog output FM to the measuring
instrument’s measuring range (indication: frequency or current).
Operation through an analog setpoint value
Configuration of the parameters
Method of operation
Inputs FW and 8 function exactly as described in the previous
example.
With digital input 3 (configured as AT), you can change over from
a voltage setpoint value (0 to 10 V) to a current setpoint value
(4 to 20 mA).
Instead of a fixed or switched connection on terminal 3, you can
set PNU C013 to 01. Digital input 3 is then configured as a break
contact (NC).
The circuit example also includes a motor PTC thermistor. It is
important to use a screened control cable and to lay the motor PTC
thermistor cable separately from the other motor cables. However,
the screen should be earthed at the inverter side only.
Figure 44:
Connect an external potentiometer
PNU
Value
Function
a001
01
Setpoint definition through control signal
terminal strip
a002
01
Start signal through FW(D)/REV terminals
F002
10
Acceleration time in s
F003
10
Deceleration time in s
–
–
FWD: Clockwise rotation on digital input FW
C008
01
REV: Start anticlockwise operation on digital
input 8
C023
00
Indication of the output frequency (analog)
through the measurement device connected to
terminals L and FM
b081
80
Adjustment of the analog frequency display
connected to terminals L and FM
REV
FWD
24 V
H
P24
FW
8
FM
L
L
O
H
R
(1 – 10 k
O
)
–
+
0 – 10 V
1 mA
PES
PES
PES
Figure 45:
Analog setpoint definition
PNU
Value
Function
A001
01
Setpoint definition through control signal terminal
strip
A002
01
Start signal through FW(D)/REV terminals
F002
10
Acceleration time in s
F003
10
Deceleration time in s
–
–
FWD: Start clockwise operation on digital input
FW
C008
01
REV: Start anticlockwise operation on digital input
8
C003
16
AT: Changeover to current setpoint value
(4 to 20 mA)