Programming the control
signal terminals
01/02 AWB8230-1415GB
68
Start/stop
Clockwise rotation (FW)
When a digital input configured as FW is activated, the motor
starts to run in a clockwise direction. When this input is deacti-
vated, the motor is decelerated to a stop under frequency inverter
control.
When the FW and REV inputs are activated simultaneously, the
motor is decelerated to a stop under frequency inverter control.
Anticlockwise rotation (REV)
When a digital input configured as REV is activated, the motor
starts to run in an anticlockwise direction. When the input is deac-
tivated, the motor is decelerated to a stop under frequency inverter
control.
Issue start signal
By default, the start signal is issued through the inputs configured
as FW or REV. If however, the start signal is currently issued
through the ON key on the keypad, enter the value 01 under
PNU A002 (start signal through FW/REV input) (
a
Section “Start
signal“, Page 123).
X
Program one of the digital inputs 1 to 8 as REV by entering the
value 01 under the corresponding PNU (C001 to C008).
By default, REV is assigned to digital input 8.
Figure 53:
Digital input FW (start/stop clockwise)
Figure 54:
Digital input 8 configured as REV (start/stop anticlock-
wise)
FWD
P24
FW
REV
P24
8
Warning!
If the frequency inverter supply voltage is applied when
the start signal is activated, the motor will start immedia-
tely. Make sure, therefore, that the start signal is not
active before the supply voltage is switched on.
Warning!
If the FW/REV input is opened (inactive state if FW/REV is
configured as a make contact) and then it is reconfigured
as a break contact, the motor will start immediately after
the reconfiguration.