4. PARAMETERS
4 - 19
4.2.2 Extension setting parameters ([Pr. PC_ _ ])
No./symbol/
name
Setting
digit
Function
Initial
value
[unit]
General
purpose
Communication
CP
PS
CP
PS
PC01
STA
JOG
operation
acceleration
time constant
Set the acceleration time constant during JOG operation.
Setting a value exceeding 20000 ms triggers [AL. F4].
For example for the servo motor of 3000 r/min rated speed, set 3000 (3 s)
to increase speed from 0 r/min to 1000 r/min in 1 s.
This parameter corresponds to "Profile acceleration (Index: 6083h)".
When this parameter is mapped to the link device of CC-Link IE Field
Network Basic, do not write the parameter value with MR Configurator2,
as the controller overwrites the parameter value written with MR
Configurator2.
Setting range: 0 to 50000
0
[ms]
PC01
STA
Acceleration
time constant
1
Set the acceleration time constant of the position command.
Setting a value exceeding 20000 ms triggers [AL. F4].
For example for the servo motor of 3000 r/min rated speed, set 3000 (3 s)
to increase speed from 0 r/min to 1000 r/min in 1 s.
Effective acceleration time constant changes with the combination of
parameter, input device and Control DI. Refer to section 4.7 for details.
This parameter corresponds to "Profile acceleration (Index: 6083h)".
When this parameter is mapped to the link device of CC-Link IE Field
Network Basic, do not write the parameter value with MR Configurator2,
as the controller overwrites the parameter value written with MR
Configurator2.
Setting range: 0 to 50000
0
[ms]
PC02
STB
JOG
operation
deceleration
time constant
Set the deceleration time constant during JOG operation.
Setting a value exceeding 20000 ms triggers [AL. F4].
This parameter corresponds to "Profile deceleration (Index: 6084h)".
When this parameter is mapped to the link device of CC-Link IE Field
Network Basic, do not write the parameter value with MR Configurator2,
as the controller overwrites the parameter value written with MR
Configurator2.
Setting range: 0 to 50000
0
[ms]
PC02
STB
Deceleration
time constant
1
Set the deceleration time constant of position command.
Setting a value exceeding 20000 ms triggers [AL. F4].
Effective deceleration time constant changes with the combination of
parameter, input device and Control DI. Refer to section 4.7 for details.
This parameter corresponds to "Profile deceleration (Index: 6084h)".
When this parameter is mapped to the link device of CC-Link IE Field
Network Basic, do not write the parameter value with MR Configurator2,
as the controller overwrites the parameter value written with MR
Configurator2.
Setting range: 0 to 50000
0
[ms]
Содержание MR-JE-C
Страница 33: ...2 SIGNALS AND WIRING 2 16 MEMO ...
Страница 37: ...3 STARTUP 3 4 MEMO ...
Страница 129: ...6 HOMING MODE 6 36 MEMO ...
Страница 169: ...7 HOW TO USE THE POINT TABLE 7 40 MEMO ...
Страница 203: ...9 HOW TO USE JOG MODE 9 12 MEMO ...
Страница 215: ...11 APPLICATION OF FUNCTIONS 11 8 MEMO ...
Страница 307: ...12 WHEN USING WITH A GENERAL PURPOSE INTERFACE 12 92 MEMO ...
Страница 309: ...MEMO ...