3. SIGNALS AND WIRING
3 - 42
Normally, connect as follows.
-10 V to +10 V
VLA
LG
SD
Servo amplifier
(b) Speed limit value selection
To select VLA (Analog speed limit) and a speed limit value of internal speed limit 1 to 7, enable SP1
(Speed selection 1), SP2 (Speed selection 2), and SP3 (Speed selection 3) with [Pr. PD03] to [Pr.
PD20].
(Note) Input device
SP3
SP2
SP1
Speed limit
0
0
0
VLA (Analog speed limit)
0
0
1
Pr. PC05 Internal speed limit 1
0
1
0
Pr. PC06 Internal speed limit 2
0
1
1
Pr. PC07 Internal speed limit 3
1
0
0
Pr. PC08 Internal speed limit 4
1
0
1
Pr. PC09 Internal speed limit 5
1
1
0
Pr. PC10 Internal speed limit 6
1
1
1
Pr. PC11 Internal speed limit 7
Note. 0: Off
1: On
When the internal speed command 1 is used to command a speed, the speed does not vary with the
ambient temperature.
(c) VLC (Limiting speed)
As in section 3.6.3 (3) (c)
(5) Torque control in torque control mode
As in section 3.6.3 (1)
(6) Torque limit in torque control mode
As in section 3.6.3 (2)
Содержание MELSERVO-JE MR-JE-100A
Страница 23: ...1 FUNCTIONS AND CONFIGURATION 1 12 MEMO ...
Страница 29: ...2 INSTALLATION 2 6 MEMO ...
Страница 91: ...3 SIGNALS AND WIRING 3 62 MEMO ...
Страница 171: ...5 PARAMETERS 5 44 MEMO ...
Страница 195: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Страница 221: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 26 MEMO ...
Страница 249: ...8 TROUBLESHOOTING 8 28 MEMO ...
Страница 254: ...9 DIMENSIONS 9 5 2 SCR connector system 3M Receptacle 36210 0100PL Shell kit 36310 3200 008 Unit mm 34 8 39 5 22 4 11 0 ...
Страница 255: ...9 DIMENSIONS 9 6 MEMO ...
Страница 263: ...10 CHARACTERISTICS 10 8 MEMO ...
Страница 293: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 30 MEMO ...