5. PARAMETERS
5 - 17
5.2.2 Gain/filter setting parameters ([Pr. PB_ _ ])
Control mode
No./
symbol/name
Setting
digit
Function
Initial
value
[unit]
P
S
T
PB01
FILT
Adaptive
tuning mode
(adaptive
filter II)
_ _ _ x Filter tuning mode selection
Set the adaptive filter tuning.
Select the adjustment mode of the machine resonance suppression filter 1. Refer to
section 7.1.2 for details.
0: Disabled
1: Automatic setting (Do not use this in the torque control mode.)
2: Manual setting
0h
_ _ x _ For manufacturer setting
0h
_ x _ _
0h
x _ _ _
0h
_ _ _ x Vibration suppression control 1 tuning mode selection
Select the tuning mode of the vibration suppression control 1. Refer to section 7.1.5
for details.
0: Disabled
1: Automatic setting
2: Manual setting
0h
PB02
VRFT
Vibration
suppression
control tuning
mode
(advanced
vibration
suppression
control II)
_ _ x _ Vibration suppression control 2 tuning mode selection
Select the tuning mode of the vibration suppression control 2. To enable the digit,
select "3 inertia mode (_ _ _ 1)" of "Vibration suppression mode selection" in [Pr.
PA24]. Refer to section 7.1.5 for details.
0: Disabled
1: Automatic setting
2: Manual setting
0h
_ x _ _ For manufacturer setting
0h
x _ _ _
0h
PB03
PST
Position
command
acceleration/d
eceleration
time constant
(position
smoothing)
This is used to set the constant of a primary delay to the position command.
You can select a control method from "Primary delay" or "Linear
acceleration/deceleration" in [Pr. PB25 Function selection B-1]. The setting range of
"Linear acceleration/deceleration" is 0 ms to 10 ms. Setting of longer than 10 ms will
be recognized as 10 ms.
When the linear acceleration/deceleration is selected, do not set the "Control mode
selection" ([Pr. PA01]) to the setting other than "_ _ _ 0". Doing so will cause the
servo motor to make a sudden stop at the time of position control mode switching.
(Example) When a command is given from a synchronizing encoder, synchronous
operation will start smoothly even if it start during line operation.
Synchronizing
encoder
Start
Servo motor
Servo amplifier
ON
OFF
With time
constant setting
Without time
constant setting
Servo motor
speed
Start
t
Setting range: 0 to 65535
0
[ms]
Содержание MELSERVO-JE MR-JE-100A
Страница 23: ...1 FUNCTIONS AND CONFIGURATION 1 12 MEMO ...
Страница 29: ...2 INSTALLATION 2 6 MEMO ...
Страница 91: ...3 SIGNALS AND WIRING 3 62 MEMO ...
Страница 171: ...5 PARAMETERS 5 44 MEMO ...
Страница 195: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Страница 221: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 26 MEMO ...
Страница 249: ...8 TROUBLESHOOTING 8 28 MEMO ...
Страница 254: ...9 DIMENSIONS 9 5 2 SCR connector system 3M Receptacle 36210 0100PL Shell kit 36310 3200 008 Unit mm 34 8 39 5 22 4 11 0 ...
Страница 255: ...9 DIMENSIONS 9 6 MEMO ...
Страница 263: ...10 CHARACTERISTICS 10 8 MEMO ...
Страница 293: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 30 MEMO ...