11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 9
(2) MR-JE-200A or more
Always remove the wiring from across P+ to D and fit the regenerative option across P+ to C. G3 and
G4 are terminals for thermal sensor. Between G3 and G4 is opened when the regenerative option
overheats abnormally.
D
P+
C
G4
G3
C
P
Regenerative option
5 m or less
Servo amplifier
Always remove the lead from across P+ to D.
(Note 3)
Cooling fan
(Note 1, 2)
Note 1. When using the MR-RB50, forcibly cool it with a cooling fan (1.0 m
3
/min or more,
92 mm × 92 mm).
2. When the ambient temperature is more than 55 °C and the regenerative load ratio
is more than 60% in MR-RB30 and MR-RB32, forcefully cool the air with a cooling
fan (1.0 m
3
/min or more, 92 mm × 92 mm). A cooling fan is not required if the
ambient temperature is 35 °C or less. (A cooling fan is required for the shaded
area in the following graph.)
100
60
0
0
Ambient temperature [°C]
35
55
A cooling fan is
not required.
A cooling fan is required.
Load ratio [%]
3. Make up a sequence which will switch off the magnetic contactor when abnormal
heating occurs.
G3-G4 contact specifications
Maximum voltage: 120 V AC/DC
Maximum current: 0.5 A/4.8 V DC
Maximum capacity: 2.4 VA
Содержание MELSERVO-JE MR-JE-100A
Страница 23: ...1 FUNCTIONS AND CONFIGURATION 1 12 MEMO ...
Страница 29: ...2 INSTALLATION 2 6 MEMO ...
Страница 91: ...3 SIGNALS AND WIRING 3 62 MEMO ...
Страница 171: ...5 PARAMETERS 5 44 MEMO ...
Страница 195: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Страница 221: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 26 MEMO ...
Страница 249: ...8 TROUBLESHOOTING 8 28 MEMO ...
Страница 254: ...9 DIMENSIONS 9 5 2 SCR connector system 3M Receptacle 36210 0100PL Shell kit 36310 3200 008 Unit mm 34 8 39 5 22 4 11 0 ...
Страница 255: ...9 DIMENSIONS 9 6 MEMO ...
Страница 263: ...10 CHARACTERISTICS 10 8 MEMO ...
Страница 293: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 30 MEMO ...