Multi-Accel/Decel time setting via Multi-function terminals
Group
Code Item
Set value Range
Initial Unit
Drive group
ACC
Accel time
-
0.0~ 6000.0 20.0
Sec
dEC
Decel time
-
0.0~ 6000.0 20.0
Sec
I/O group
I17
Multi-function input terminal P1
function selection
0
0 ~ 27
0
I18
Multi-function input terminal P2
function selection
1
1
I19
Multi-function input terminal P3
function selection
8
2
I20
Multi-function input terminal P4
function selection
9
3
I21
Multi-function input terminal P5
function selection
10
4
I34
Multi-step Accel time 1
-
0.0~ 6000.0 3.0
Sec
~
~
I47
Multi-step Decel time 7
-
9.0
Select terminals for Accel/Decel time command signal from multi-function input terminals (P1 ~ P5).
If Accel/Decel time is set via P3 ~ P5 terminals, I19 ~ I21 codes are set to 8,9,10.
Multi-step Accel/Decel time 0 is set at ACC, dEC in Drive group.
Multi-step Accel/Decel time 1 ~ 7 is set at I34 ~ I47.
Accel / Decel