Chapter 7 Basic Functions
7-3
Cx2000 AC Drive
I7 ~ I10: the input voltage range and corresponding frequency of V1 terminal can be set.
Ex) when minimum (+) input voltage is 2V with corresponding frequency 10Hz and Max voltage is 8V with
run req. 50Hz.
Wire the terminals as shown below
Terminal AI setting frequency(dial J1 to terminal I): input 0 ~ 20[mA]
Group
Code
Item
Set value Range
Initial Unit
Drive group 0.00
Target frequency
-
0.00 ~ 400.00 0.00
Hz
Frq
Frequency setting mode
4
0 ~ 8
0
I/O group
I11
Filter time constant for I input
-
0 ~ 9999
10
I12
I input minimum current
-
0 .00~ 20.00
4.00
mA
I13
Corresponding frequency of I
input minimum current
-
0.00 ~ 400.00 0.00
Hz
I14
I input maximum current
-
0.00 ~ 20.00
20.00
mA
I15
Corresponding frequency of I
input maximum current
-
0.00 ~ 400.00 60.00
Hz
Set Frq code of Drive group to 4.
Set frequency through input 0~20mA on AI terminal and CM terminal of inverter. Dial J1 to I terminal.
V R
A IN
(V 1 )
C M
电 位 器 接 线
wiring diagram of potentiometer