Chapter 8 Application
8-8
Cx2000 AC Drive
H 8
Dwell time
-
0.0 ~ 10.0
0.0
sec
In this setting, motor begins to accelerate after dwell operation is executed for dwell time at
the dwell frequency.
It is mainly used to release mechanical brake in elevators after operating at dwell
frequency.
Dwell frequency: This function is used to output torque in an intended direction. It is useful in hoisting
applications to get enough torque before releasing a mechanical brake. Rated Slip frequency is
calculated by the formula shown below.
8.6 Slip compensation
Group
Code
Item
Set Value Setting Range Initial
Unit
Function
group 2
H30
Motor type select
-
0.1 0~ 11.00
0.75
H31
Number of motor poles
-
2 ~ 12
4
H32
Rated slip frequency
-
0.00 ~ 10.00
2.33
Hz
H33
Motor rated current
-
0.5 ~ 150.0
26.3
A
H34
Motor No Load Current
-
0.1 ~ 50.0
11.0
A
H36
Motor efficiency
-
50 ~ 100
87
%
H37
Load inertia rate
-
0 ~ 2
0
H40
Control mode select
1
0 ~ 3
0
Set H40 – [Control mode select] to 1 (Slip compensation) in the function group 2
This function enables the motor to run in constant speed by compensating inherent slip in an
induction motor.
H30: Set the motor type
H30
Motor type select
0.1
0.1kW
~
11.0
11.0kW
Frequency
R un C om m and
D w ell tim e
D w ell freq.
Start freq.