![Larsen & Toubro C*2000 Series Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/larsen-and-toubro/c-2000-series/c-2000-series_user-manual_676507029.webp)
Chapter 3 Peripheral equipment
3-2
Cx2000 AC Drive
3.2 Recommend breaker and breaker specification
NOTE
1) The current of selected breaker shall be 1.5 to 2 times of rated current.
2) In order to prevent the damage of AC equipment because of fault current, please use MCCB to
replace overload protection device (150% rated output 1 minute protection)
Inverter model
L&T MCCB/Amp
Electromagnetic
contactor
Single phase
230V
LTVF-C10001BAA
DM16/2.5
MNX 9-2P
LTVF-C10002BAA
DM16/6.3
MNX 9-2P
LTVF-C10003BAA
DM16/12
MNX 9-2P
LTVF-C10005BAA
DM100/25
MNX 9-2P
LTVF-C10008BAA
DM100/30
MNX 12-2P
LTVF-C10011BAA
DM100/50
MNX 18-2P
HD
ND
Three phase
230V
LTVF-C20001BAA
DM16/1.6
DM16/2.5
MO9
LTVF-C20002BAA
DM16/4
DM16/4
MO9
LTVF-C20003BAA
DM16/4
DM16/7.5
MO9
LTVF-C20006BAA
DM16/12
DM16/16
MO9
LTVF-C20010BAA
DM16/16
DM100/25
MO-12
LTVF-C20012BAA
DM100/25
DM100/25
MO-18
LTVF-C20018BAA
DM100/35
DM100/50
MO-32
LTVF-C20030BAA
DM100/50
DM100/60
MO-40
LTVF-C20040BAA
DM100/60
DM100/80
MO-50
Three phase
415V
LTVF-C40002BAA
DM16/4
DM16/5
MO9
LTVF-C40003BAA
DM16/7.5
DM16/10
MO9
LTVF-C40005BAA
DM16/10
DM16/12
MO9
LTVF-C40007BAA
DM16/12
DM16/16
MO-12
LTVF-C40010BAA
DM100/25
DM100/30
MO-18
LTVF-C40016BAA
DM100/25
DM100/30
MO-32
LTVF-C40023BAA
DM100/30
DM100/50
MO-32