![Larsen & Toubro C*2000 Series Скачать руководство пользователя страница 85](http://html1.mh-extra.com/html/larsen-and-toubro/c-2000-series/c-2000-series_user-manual_676507085.webp)
Chapter 7 Basic Functions
7-4
Cx2000 AC Drive
Setting of keypad potentiometer V2+ terminal AI 0 ~ 20mA (dial J1 to terminal I)
Group
Code
Item
Set value Range
Initial
Unit
Drive group 0.00
Target frequency
-
0.00 ~ 400.00 0.00
Hz
Frq
Frequency setting mode
5
0 ~ 8
0
Set Freq code of Drive group to 5.
The main/ auxillary speed is adopted to adjust so as to reach the override function. (
Override function
available using Main/Auxiliary speed adjustment)
Relevant codes: I 2 ~ I 5
,
I11 ~ I15
Override function is to gain precise control and fast response by combining Main and Auxiliary speed input.
Fast response can be achieved by Main speed and precise control can be accomplished by Aux. speed if
the accuracy of Main/Aux speed is set differently.
Follow the setting below when Main speed is given via 0 ~ 20mA with Aux. speed via keypad potentiometer
(0 ~ 5V).
When override function is used, select the Main/Aux. speed according to loads used.
Group
Code Item
Set Value
Unit
I/O group
I 2
V2 input Min voltage
0.00
V
I 3
Corresponding frequency of V2 input Min
voltage
0.00
Hz
I 4
V2 input Max voltage
5.00
V
I 5
Corresponding frequency of V2 input Max
voltage
5.00
Hz
I12
I input Min voltage
4.00
mA
I13
Corresponding frequency of I input Min current 0.00
Hz
I14
I input Max current
20.00
mA
I15
Corresponding frequency of I input Max current 60.00
Hz
After the setting is made as above, if 2.5V is applied to V2 terminal with 12mA given to terminal I, output
frequency would be 32.5Hz. If 2.5V is applied to V2 terminal with 5V given to terminal V1, output frequency
would be 32.5Hz, too.
Содержание C*2000 Series