Chapter 4 Parameter setting
4-14
Cx2000 AC Drive
Frequency Setting via Terminal AI (V) and Driving via Terminals
1
-. Apply power to the inverter.
2
-. 0.00 is displayed on the inverter keypad.
-. Press the Up (
) key four times.
3
-. Freq. is displayed. Frequency setting mode is selectable.
-. Press the ENT key.
4
-. Present frequency setting method is set to 0 (frequency setting via keypad).
-. Press the Up (
) key three times.
5
-. 3 is displayed [frequency setting via terminal AIN (V1)]
-. Press the ENT key.
6
-. Press the ENT key again after “3” is blinking.
-. Freq. is displayed; the frequency setting method is changed into terminal
AIN (V) setting frequency.
-. Press the Down (
) key four times to move to frequency display status.
-. V1 voltage is adjusted so that output frequency is 10.00 Hz.
7
-. Turn off (ON) the switch between P1 (FX) and CM terminals.
-. RUN (operating) lamp on the inverter keypad begins to blink with FWD (Forward
Run) lamp lit and accelerating frequency displayed on the keypad.
-. Run frequency reaches 10 Hz.
-. Turn off the switch between P1 (FX) and CM terminals.
8
-. Run (operating) lamp on the inverter keypad is blinking over again, and the
number displayed indicates the decelerating frequency.
-. After run frequency reaches 0Hz, Run (operating) and FWD (forward run) lamps
are blacked out, 10.00 is displayed on the keypad.
Connection diagram
Run curve