Chapter 5 – Function list
5-24
Cx2000 AC Drive
Input/output group
LED
display
Address for
comm
Parameter
name
Range
Description
Factory
defaults
Adj.
During
run
Page
I11
140B
I input
0
~
9999
Sets simulation input A1 (terminal 1) input
filtering wave time constant.
10
O
7-3
I12
140C
I input Min
current
0.00
~
20.00
[mA]
Sets simulation input A1 (terminal 1) Min.
input current
4.00
O
I13
140D
1 input Min.
current
corresponding
frequency
0.00
~
400.00
[Hz]
Sets simulation input A1 (terminal 1) Max.
input current, corresponding frequency.
0.00
O
I14
140E
I input Max
current
0.00
~
20.00
[mA]
Sets the Maximum current of I input.
20.00
O
I15
140F
1 input Max.
current
corresponding
frequency
0.00
~
400.00
[Hz]
Sets simulation input A1 (terminal 1) Max.
input current, corresponding frequency.
60.00
O
I16
1410
Criteria for
Analog Input
Signal loss
0
~
2
0: Disabled
1: activated below half of set value.
2: activated below set value.
0
O
10-7