Chapter 8 Application
8-4
Cx2000 AC Drive
Function group 1: set the jog frequency in F20.
Select a terminal to use for the Jog-FX from multi-function input terminals (P1~P5)
If P4 is set for jog FX, set I20 to 26 (jog-FX) in I/O group.
Jog frequency can be set within the range of F21 (Max frequency) and F23 (Start frequency).
The following diagram is an example when target frequency is 30Hz and Jog frequency is 10 Hz.
P1
CM
FX : I 17 = 0
JOG : I20=26
P4
Freq.
F
20
30Hz
P4
Run Command
8.3 UP/Down operation
UP/Down storage function
Group
Code
Item
Set Value
Setting
Range
Initial
Unit
Drive group
Frq
Frequency setting mode
8
0 ~ 8
0
I/O group
I17
Multi-function input terminal P1
selection
0
0 ~ 27
0
I19
Multi-function input terminal P3
selection
25
2
I20
Multi-function input terminal P4
selection
15
3
I21
Multi-function input terminal P5
selection
16
4
Function
group 1
F63
Up-Down frequency save select
-
0 ~ 1
0
F64
Up-Down frequency storage
-
0.00
Select 8 in Frq code of drive group
Select the terminal which uses as a up-down drive among multi-function input terminals(P1~P5)