![Larsen & Toubro C*2000 Series Скачать руководство пользователя страница 89](http://html1.mh-extra.com/html/larsen-and-toubro/c-2000-series/c-2000-series_user-manual_676507089.webp)
Chapter 7 Basic Functions
7-8
Cx2000 AC Drive
7.3 Operating command setting method
Operation via keypad RUN key and STOP/RST key
Group
Code Item
Set value Range
Initial Unit
Drive group
drv
Drive mode
0
0 ~ 3
1
drC
Selection of motor rotation
direction
-
F,r
F
It is used only when the inverter uses the keypad control.
Set drv code of Drive group to 0.
Acceleration is started upon pressing the Run key while operating frequency is set. Motor
decelerates to stop by pressing the STOP/RST key.
Selecting the rotation direction of motor is available at drC - [Selection of motor rotation direction]
when operating command is issued via keypad.
drC
Operating
direction of motor
F
Forward
r
Reverse
Operating command 1 via FX, RX terminals of inverter
Group
Code Item
Setting
Range Initial Unit
Drive group
drv
Drive mode
1
0 ~ 3
1
I/O group
I17
Multi-function input terminal P1
function selection
0
0 ~ 27 0
I18
Multi-function input terminal P2
function selection
1
0 ~ 27 1
Set drv of Drive group to 1.
When the multi-function input terminals P1 and P2 are used for FX and RX, I17 and I18 in I/O group
are set to 0 and 1 respectively.
“FX” is forward run command and “RX” reverse run.
Motor is stopped when FX/RX terminal is ON/OFF at the same time.
C ounter-clockw ise direction
FX
R X
Freq.