Chapter 9 Monitoring
9-10
Cx2000 AC Drive
When setting I52 and I53 to 30.00Hz and 10.00 Hz, respectively
5 : Overload (OLt)
Refer to page 10-2.
6 : Inverter Overload (IOLt)
Refer to page 10-5
7 : Motor stall (STALL)
Refer to page 10-3.
8 : Over voltage trip (Ovt)
Activated when over voltage trip occurs due to DC link voltage exceeded 400Vdc for 230V class and
820Vdc for 415V class.
9: Low voltage trip (Lvt)
Activated when low voltage trip occurs due to DC link voltage under 180Vdc for 230V class and 360Vdc for
415V class
10: Inverter heatsink overheat (OHt)
Activated when the heatsink is overheated
11: Command loss
Activated when Analog (V1,I) and RS485 communication commands are lost.
12: During operation
Activated when run command is input and inverter outputs its voltage.
Freq.
MO
Run command
25Hz
30Hz
Freq.
MO
Run command