Chapter 8 Application
8-9
Cx2000 AC Drive
H31: Enter the pole number on the Motor nameplate.
H32: Enter the slip frequency in accordance with the following formula and motor nameplate.
120
P
rpm
f
f
r
s
Where,
fs
= Rated slip frequency
f r
= Rated frequency
rpm
= Motor rated RPM
P
= Motor pole number
Ex) Rated freq.: 60Hz, Rated RPM: 1740rpm, Poles: 4,
H33: Enter the motor nameplate rated current.
H34: Enter the measured current when the motor is running at rated frequency after the load is
removed. Enter 50% of the rated motor current when it is difficult to measure the motor no load current.
H36: Enter motor efficiency on the nameplate.
H37: Select load inertia based on motor inertia as shown below.
H37
Load inertia rate
0
Less than 10 times motor inertia
1
About 10 times motor inertia
2
Greater than 10 times motor inertia
As the loads are heavier, the speed gap between rated RPM and synchronous speed is widening (see
the figure below). This function compensates for this inherent slip.
Hz
f
s
2
120
4
1740
60
S yn ch ro n o u s
sp e e d
M o to r re te d
R P M
R P M
L o a d
S lip
co m p e n sa tio n