Chapter 8 Application
8-16
Cx2000 AC Drive
remove the load from the motor shaft, enter the value either 40 to 50% of the H33 – [Motor rated
current] or the factory default.
In case that occur torque riffle while high speed driving, lower H34-[No load current] to 30%.
H42, H44: Enter the value of the parameter measured during H41 – [Auto tuning] or the factory default.
F14: This parameter accelerates the motor after pre-exciting the motor for the set time. The amount of
the pre-exciting current is set in H34- [Motor no load current].
Directly enter the motor nameplate value except motor rating when 0.2kW is used.
Factory default by motor ratings
Input
voltage
Motor
rating [kW]
Current
rating [A]
No-load
Current [A]
Rated slip
freq [Hz]
Stator
Resistance [Ω]
Leakage
inductance [mH]
230
0.1
0.6
0.4
2.00
30.00
240.00
0.2
1.1
0.6
2.33
14.00
122.00
0.4
1.8
1.2
3.00
6.7
61.00
0.75
3.5
2.1
2.33
2.46
28.14
1.1
4.8
2.1
2.33
2.46
28.14
1.5
6.5
3.0
2.33
1.13
14.75
2.2
8.8
4.4
2.00
0.869
11.31
3.0
11.6
4.4
2.00
0.869
11.31
3.7
12.9
4.9
2.33
0.5
5.41
4.0
14.6
4.9
2.33
0.5
5.41
5.5
19.7
6.6
2.33
0.314
3.6
7.5
26.3
11.0
2.33
0.196
2.89
11.0
37.0
12.5
1.33
0.120
2.47
415
0.1
0.4
0.3
2.00
56.00
600.00
0.2
0.7
0.4
2.33
28.00
300.00
0.4
1.1
0.7
3.00
14.00
177.86
0.75
2.0
1.3
2.33
7.38
88.44
1.1
2.4
1.3
2.33
7.38
88.44
1.5
3.7
2.1
2.33
3.39
44.31
2.2
5.1
2.6
2.00
2.607
34.21
3.0
5.8
2.6
2.00
2.607
34.21
3.7
6.5
3.3
2.33
1.5
16.23
4.0
8.4
3.3
2.33
1.5
16.23
5.5
11.3
3.9
2.33
0.94
10.74
7.5
15.2
5.7
2.33
0.52
8.80
11.0
22.6
7.5
1.33
0.36
7.67