Safety Instructions
iii
Cx2000 AC Drive
OTHER PRECAUTIONS
(1) Handling and installation
Handle according to weight of the product.
Do not stack the inverter boxes higher than the number recommended.
Install according to instructions specified in this manual.
Do not open the cover during delivery.
Do not place heavy items on the inverter.
Check the inverter mounting orientation is correct.
The inverter is precise equipment. So do not drop the inverter or subject it to impact.
Follow your national electrical code for grounding. Recommended ground impedance for 230V
Drives is below 100 ohm and for 415V class below 10 ohm.
This series inverter contains ESD sensitive parts. Take protective measures against ESD
before touching the PCB for inspection or installation.
Use the inverter under the following environmental conditions:
E
nv
iro
nm
en
t
Surrounding temperature
- 10 C ~ +50 C (non-freezing)
Relative humidity
90% RH or less (non-condensing)
Storage temperature
- 20 C ~ +65 C
Environment
Protected from corrosive gas, combustible
gas, oil mist or dust.
Altitude, vibration
Max. 1,000m above sea level, Max. 5.9m/
sec²(=0.6g) or less
Atmospheric pressure
70 ~ 106 kPa
(2) Wiring
Do not connect a power factor correction capacitor, surge suppressor, or RFI filter to the output of
the inverter.
The connection orientation of the output cables U, V, W to the motor will affect the direction of
rotation of the motor.
Incorrect terminal wiring could result in the equipment damage.
Wrong connection of input terminal (R, S, T) and output terminal (U, V, W) will damage the
inverter.
Only authorized personnel familiar with L&T inverter should perform wiring and inspections.
Always install the inverter before wiring. Otherwise, you may get an electric shock or have bodily
injury.